JULIANSYAH, ANGGA (2015) ANALISA KEANDALAN RELAI JARAK SEBAGAI PENGAMAN UTAMA PADA SALURAN UDARA TEGANGAN TINGGI 70 KV DI GARDU INDUK BOOM BARU – SEDUDUK PUTIH. Other thesis, Politeknik Negeri Sriwijaya.
|
Text (COVER)
COVER.pdf Download (116kB) | Preview |
|
|
Text (BAB I PENDAHULUAN)
BAB-1.pdf Download (54kB) | Preview |
|
|
Text (BAB II TINJAUAN PUSTAKA)
BAB-2.pdf Download (346kB) | Preview |
|
![]() |
Text (BAB III KEADAAN UMUM)
BAB-3.pdf Restricted to Repository staff only Download (931kB) |
|
![]() |
Text (BAB IV PEMBAHASAN)
BAB-4.pdf Restricted to Repository staff only Download (135kB) |
|
|
Text (BAB V KESIMPULAN DAN SARAN)
BAB-5.pdf Download (47kB) | Preview |
|
|
Text (DAFTAR PUSTAKA)
DAFTAR-PUSTAKA.pdf Download (21kB) | Preview |
Abstract
The final report entitled “The Analysis Of Distance Relay Reliability As A Main Protection On High Voltage 70 kV At Boom Baru – Seduduk Putih Substation”. The purpose of this final report are knowing the procedure of distance relay, the setting calculation of distance relay dan determine whether the distance relays at Boom Baru substations is reliable or not. The data collection method are used observation and interviews. Data obtained from Transmission Service Unit (UPT) PT. PLN (Persero) Palembang and Boom Baru substations. The procedure of distance relay is the relay will trip when the value of impedance due to the interference is smaller than the impedance setting of distance relays at Boom Baru substations. Setting value obtained from calculation is zone 1 of 0.15 ∠ 55.7 ° with time of 0 seconds, zone 2 at 0.2232 ∠ 55.7 ° with time of 0.4
Item Type: | Thesis (Other) |
---|---|
Uncontrolled Keywords: | The data collection method are used observation and interviews. Data obtained from Transmission Service Unit (UPT) PT. PLN (Persero) Palembang and Boom Baru substations. The procedure of distance relay is the relay will trip when the value of impedance due to the interference is smaller than the impedance setting of distance relays at Boom Baru substations. Setting value obtained from calculation is zone 1 of 0.15 ∠ 55.7 ° with time of 0 seconds, zone 2 at 0.2232 ∠ 55.7 ° with time of 0.4 |
Subjects: | T Technology > TK Electrical engineering. Electronics Nuclear engineering |
Divisions: | Electrical Engineering > Undergraduate Theses |
Depositing User: | Mrs Trisni Handayani |
Date Deposited: | 03 Nov 2015 07:50 |
Last Modified: | 03 Nov 2015 07:50 |
URI: | http://eprints.polsri.ac.id/id/eprint/1741 |
Actions (login required)
![]() |
View Item |