ANALISA GANGGUAN TRANSFORMATOR DISTRIBUSI 20 kV/400 V DI PT.PLN RAYON KENTEN PALEMBANG

SILVIYANTY, WILY (2014) ANALISA GANGGUAN TRANSFORMATOR DISTRIBUSI 20 kV/400 V DI PT.PLN RAYON KENTEN PALEMBANG. Other thesis, Politeknik Negeri Sriwijaya.

[img]
Preview
Text (Cover)
COVER.pdf

Download (522kB) | Preview
[img]
Preview
Text (BAB I PENDAHULUAN)
bab 1.pdf

Download (247kB) | Preview
[img]
Preview
Text (BAB II TINJAUAN PUSTAKA)
bab 2.pdf

Download (758kB) | Preview
[img] Text (BAB III METODOLOGI PENELITIAN)
bab 3.pdf
Restricted to Repository staff only

Download (181kB)
[img] Text (BAB IV HASIL DAN PEMBAHASAN)
bab 4.pdf
Restricted to Repository staff only

Download (753kB)
[img]
Preview
Text (BAB V KESIMPULAN DAN SARAN)
bab 5.pdf

Download (436kB) | Preview
[img]
Preview
Text (DAFTAR PUSTAKA)
DAFTAR PUSTAKA.pdf

Download (83kB) | Preview
[img]
Preview
Text (Lampiran)
LAMPIRAN.pdf

Download (18MB) | Preview

Abstract

The transformer is a very important part in the distribution of electrical energy. Therefore, the transformer must be maintained properly so that reliability is maintained. Even so, the transformer still be getting a disturbance. To minimize , it need analysis of the disturbance in order to avoid the another transformer to get the same disturbance. The final report is analyze the way a visual observation on the part of the substation transformers and components and perform measurements on the transformer to determine the insulation resistance. The result of these observations by a case study on I. 533 substation, the capacity is 400 kVA and the voltage is 20 kV/400 V that there is damage of bushing. The bushing is burned the temperature is , Fuse cut out is disconnected, it caused by the S phase is disconnect, so that the currents are very large and more than the setting value of the fuse cut-out. The short-circuit current is 14.433,8 A and the rated current of the fuse cut-out is 16 A. Keywords: Distribution Transformer, Fault Transformer, Short Circuit

Item Type: Thesis (Other)
Uncontrolled Keywords: Distribution Transformer, Fault Transformer, Short Circuit
Subjects: T Technology > TJ Mechanical engineering and machinery
Divisions: Telecommunication Engineering > Undergraduate Theses
Depositing User: Mr Bambang Anthony
Date Deposited: 21 Jan 2016 10:12
Last Modified: 21 Jan 2016 10:12
URI: http://eprints.polsri.ac.id/id/eprint/357

Actions (login required)