ANALISA KETIDAKSEIMBANGAN BEBAN PADA TRANSFORMATOR I. 974 PENYULANG PANDU PT. PLN (PERSERO) RAYON SUKARAMI PALEMBANG

INTAN YOLANDA, RIZKA (2014) ANALISA KETIDAKSEIMBANGAN BEBAN PADA TRANSFORMATOR I. 974 PENYULANG PANDU PT. PLN (PERSERO) RAYON SUKARAMI PALEMBANG. Other thesis, Politeknik Negeri Sriwijaya.

Full text not available from this repository.

Abstract

RIZKA INTAN YOLANDA 0611 3031 1452 MAJORING ELECTRICAL ENGINEERING Unbalance Load on the each phase of distribution lines substation in the I. 974 at PT. PLN (Persero) Rayon Sukaranmi to reduce neutral currents carried the burden of load balancing. And results of measurements and calculations show that the percentage of load imbalance each lines after the balancing the load is reduced. In the majors B from 72% to 6,67%, majoring C from 77.67% to 6.33%, majoring D from 72% to 6,67%,. Reduced the percentage of load imbalance with the current flowing in the neutral conductor is also reduced. In I. 974 substation measurement we cam see which phase that have unbalance load. Losses due to the current in the neutral conductor of the transformer in the LWBP is 6,285 kW and then balanced to LWBP is 0,079 kW. And WBP after balance is 26,091 kW and then balanced to LWBP is 0,221 kW. So, the bigger unbalance load happen, the losses cause by neutral conductor will be bigger. Key Words : Unbalance Load, Neutral Current, Losses

Item Type: Thesis (Other)
Uncontrolled Keywords: Unbalance Load, Neutral Current, Losses
Subjects: T Technology > TJ Mechanical engineering and machinery
Divisions: Telecommunication Engineering > Undergraduate Theses
Depositing User: Mr Bambang Anthony
Date Deposited: 21 Jan 2016 10:13
Last Modified: 21 Jan 2016 10:13
URI: http://eprints.polsri.ac.id/id/eprint/361