PENGARUH KEGAGALAN MINYAK TRANSFORMATOR DAYA 18.5 MVA PLTG UNIT 1 DI PT PLN (PERSERO) SEKTOR PEMBANGKITAN KERAMASAN

SANTOSO, BUDI PUJO (2016) PENGARUH KEGAGALAN MINYAK TRANSFORMATOR DAYA 18.5 MVA PLTG UNIT 1 DI PT PLN (PERSERO) SEKTOR PEMBANGKITAN KERAMASAN. Other thesis, POLITEKNIK NEGERI SRIWIJAYA.

Full text not available from this repository.

Abstract

In the power transformer frequent disturbances that can cause failure of the transformer. It is necessary for the care and maintenance of power transformers, one with transformer oil testing is test DGA. The test is performed to determine whether there is an abnormality in the transformer. DGA testing a transformer condition analysis is performed based on the amount of gas dissolved in transformer oil. In this paper, using Roger's ratio for failure analysis of transformer failure. Roger's Ratio Method showed the occurrence of partial discharge and data TDCG shows the results of 5729 ppm indicating that the transformer is in a state of decomposition 4 which has a high level of oil. Calculation of the current rise in consecutive years 2014-2016 amounted to 171 kA, 174 kA and 195 kA and the calculation of the temperature are 154.76 ° C, 159.34 ° C and 201.6 ° C. The calculation of current and temperature rise by DGA testing indicates that the current rise in the transformer effect on temperature rise in transformer insulating oil.

Item Type: Thesis (Other)
Uncontrolled Keywords: DGA, Gas Terlarut, Rogers ratio, Arus, Temperatur
Subjects: T Technology > TK Electrical engineering. Electronics Nuclear engineering
Divisions: Electrical Engineering > Undergraduate Theses
Depositing User: Mrs Trisni Handayani
Date Deposited: 31 Jul 2017 08:31
Last Modified: 31 Jul 2017 08:31
URI: http://eprints.polsri.ac.id/id/eprint/3821