PENGAMAN ARUS LEBIH BERBASIS SCADA PADA JARINGAN DISTRIBUSI PENYULANG TENGGIRI DI AREA PENGATUR DISTRIBUSI (APD) PT. PLN (PERSERO) PALEMBANG

GULTOM, BENYAMIN IGNATIUS (2015) PENGAMAN ARUS LEBIH BERBASIS SCADA PADA JARINGAN DISTRIBUSI PENYULANG TENGGIRI DI AREA PENGATUR DISTRIBUSI (APD) PT. PLN (PERSERO) PALEMBANG. Other thesis, Politeknik Negeri Sriwijaya.

Full text not available from this repository.

Abstract

Overcurrent is a disturbance that often occurs in the distribution network. Overcurrent can result in damage to the unit and dangerous to human, therefore, SCADA based overcurrent security is installed so that it detects disturbance and secure it. By using the formula of short circuit current and the current setting and TMS relay protection, so obtained setting of current on the protection relay is 2.35 A and TMS is 0.12. The operation of overcurrent safety can be done remotely using SCADA system, which utilizes communication network with a frequency from 900 until 907,5 MHz. By using the SCADA system disturbance can be isolated and known the location of disturbance, so that maintenance and repair can be done. After maintenance and repair is done, CB can be connected again by using a SCADA system. Keywords : SCADA, Security Over current, and Relay Protection

Item Type: Thesis (Other)
Uncontrolled Keywords: SCADA, Security Over current, and Relay Protection
Subjects: T Technology > TK Electrical engineering. Electronics Nuclear engineering
Divisions: Electrical Engineering > Undergraduate Theses
Depositing User: Mrs Trisni Handayani
Date Deposited: 18 Nov 2015 08:43
Last Modified: 18 Nov 2015 08:43
URI: http://eprints.polsri.ac.id/id/eprint/1729