Habibi, M. Rafii (2026) Analisis Kondisi Isolator pada Current Limiting Reactor Menggunakan Pengukuran UHF Partial Discharge dan Thermal Infrared. Diploma thesis, Politeknik Negeri Sriwijaya.
This is the latest version of this item.
|
Text (COVER)
COVER.pdf - Published Version Download (717kB) | Preview |
|
|
Text (ABSTRAK)
ABSTRAK.pdf - Published Version Download (225kB) | Preview |
|
|
Text (BAB I PENDAHULUAN)
BAB I.pdf - Published Version Restricted to Repository staff only Download (246kB) |
||
|
Text (BAB II TINJAUAN PUSTAKA)
BAB II.pdf - Published Version Restricted to Repository staff only Download (475kB) |
||
|
Text (BAB III METODOLOGI PENELITIAN)
BAB III.pdf - Published Version Restricted to Repository staff only Download (256kB) |
||
|
Text (BAB IV PEMBAHASAN)
BAB IV.pdf - Published Version Restricted to Repository staff only Download (513kB) |
||
|
Text (BAB V KESIMPULAN DAN SARAN)
BAB V.pdf - Published Version Restricted to Repository staff only Download (178kB) |
||
|
Text (DAFTAR PUSTAKA)
DAFTAR PUSTAKA.pdf - Published Version Restricted to Repository staff only Download (132kB) |
||
|
Text (LAMPIRAN)
LAMPIRAN.pdf - Published Version Restricted to Repository staff only Download (3MB) |
Abstract
Penelitian ini dilatarbelakangi oleh pentingnya menjaga keandalan isolator tumpu Current Limiting Reactor (CLR) di PT X Kota Palembang dari risiko kegagalan isolasi. Tujuan penelitian adalah menganalisis kondisi kelayakan isolator melalui integrasi pengujian elektrikal Ultra High Frequency Partial Discharge (UHF PD) dan pengujian termal Thermal Infrared berbasis metode perbandingan antar-fasa berbeban sama \left(T_{ref}\right), serta menyusun matriks keputusan pemeliharaannya. Berdasarkan 220 data UHF PD, kondisi isolator didominasi kategori Good (77,73%), namun mendeteksi 14,54% kondisi Bad akibat kebocoran listrik internal. Sebaliknya, dari 164 data Thermal Infrared, populasi terpusat pada kategori Moderate (72,56%) akibat ketidakseimbangan panas permukaan luar. Perbedaan (gap) hasil ini membuktikan kedua alat memiliki fokus sensitivitas yang saling melengkapi. Integrasi kedua data ke dalam Matriks Keputusan Pemeliharaan Berbasis Kondisi (Condition-Based Maintenance) berhasil mengeliminasi titik buta (blind spot) penilaian risiko aset, serta menghasilkan empat skala prioritas rekomendasi tindakan praktis yang akurat untuk diimplementasikan di lapangan. This research was initiated by the vital importance of maintaining the reliability of post insulators on Current Limiting Reactors (CLR) at PT X Palembang City against the risk of catastrophic insulation failure. The objective of this study was to analyze the operational condition of the insulators through the data integration of electrical Ultra High Frequency Partial Discharge (UHF PD) testing and thermal Thermal Infrared testing based on the phase-to-phase comparison method under identical load conditions \left(T_{ref}\right) , as well as to formulate its condition-based maintenance decision matrix. Based on 220 UHF PD data points, the insulator conditions were dominated by the "Good" category (77.73%), yet it successfully detected 14.54% of "Bad" conditions due to internal electrical leakage. Conversely, from 164 Thermal Infrared data points, the population was heavily concentrated in the "Moderate" category (72.56%) due to external surface thermal imbalances. This detection gap proves that both instruments possess distinct, complementary sensitivity focuses. Integrating both datasets into a Condition-Based Maintenance (CBM) Decision Matrix successfully eliminated the assessment blind spots of asset risks and provided four accurate, priority-scaled recommendations for practical field implementation.
| Item Type: | Thesis (Diploma) |
|---|---|
| Uncontrolled Keywords: | Isolator, UHF PD, Thermal Infrared, CLR, Sensitivitas Insulator, UHF PD, Thermal Infrared, CLR, Sensitivity. |
| Subjects: | T Technology > TK Electrical engineering. Electronics Nuclear engineering |
| Divisions: | Electrical Engineering > Undergraduate Theses |
| Depositing User: | Pustaka Teknik Elektro |
| Date Deposited: | 28 Jul 2026 02:51 |
| Last Modified: | 28 Jul 2026 02:51 |