ANALISA TAHANAN PENTANAHAN TRAFO DAYA 60 MVA DI TRANSMISI GARDU INDUK SIMPANG TIGA INDRALAYA

LITRA, RAHMAD (2016) ANALISA TAHANAN PENTANAHAN TRAFO DAYA 60 MVA DI TRANSMISI GARDU INDUK SIMPANG TIGA INDRALAYA. Other thesis, POLITEKNIK NEGERI SRIWIJAYA.

[img]
Preview
Text
cover, daftar isi, motto,abstrak dan kata penghantar.pdf

Download (444kB) | Preview
[img]
Preview
Text
BAB I.pdf

Download (102kB) | Preview
[img]
Preview
Text
BAB II.pdf

Download (1MB) | Preview
[img] Text (BAB III Metode Penelitian)
BAB III.pdf
Restricted to Repository staff only

Download (441kB)
[img]
Preview
Text
Diagram Flow Chat.pdf

Download (111kB) | Preview
[img] Text (BAB IV Pembahasan)
BAB IV.pdf
Restricted to Repository staff only

Download (360kB)
[img]
Preview
Text
BAB V.pdf

Download (99kB) | Preview
[img]
Preview
Text
Daftar Pustaka.pdf

Download (5kB) | Preview

Abstract

The process distribution electrical energy of power transformer is really important, especially, 60 MVA of power transformer that use to decrease 150 Kv high voltage into 20 Kv middle voltage. Thefefore, it is necessary to provide pacification of transformer security that can protect transformer from variousdisturbance. Besides that, the pacification also can restrict the disturbance current mat can, give endanger for human and grounding system. The problem happend about security of grounding system are “how keep the establishment value of available grounding ristance ? “and to know “is the grounding resistance on the power transformer follow or not the certainly grounding resistance that should order 5 ohm. from the problem above, it means that we can do the measurement, calculation and comparison between measurement and calculation from 60 MVA power transformer of grounding system, based on data that the writer got, the result of measurement was 0,2 ohm and the result of calculation was 0,24 ohm. Therefore, the comparison between measurement and calculation was similarity. In brief, the writer conclude that the value grounding system resistance of 60 mva power transformer already fulfill certainly. The writer suggest that the staff should make schedule for carryiing out the grounding system regularly.

Item Type: Thesis (Other)
Uncontrolled Keywords: Transformator daya 60 MVA,Tahanan Pentanahan, nilai pengukuran,nilai perhitungan
Subjects: T Technology > TK Electrical engineering. Electronics Nuclear engineering
Divisions: Electrical Engineering > Undergraduate Theses
Depositing User: Mrs Trisni Handayani
Date Deposited: 01 Aug 2017 03:14
Last Modified: 01 Aug 2017 03:14
URI: http://eprints.polsri.ac.id/id/eprint/3833

Actions (login required)