ANALISA SETTING OVER CURRENT RELAY PADA PENYULANG BANTENG DI GARDU INDUK BUKIT SIGUNTANG

ANGGRAINI, CHARISA (2014) ANALISA SETTING OVER CURRENT RELAY PADA PENYULANG BANTENG DI GARDU INDUK BUKIT SIGUNTANG. Other thesis, Politeknik Negeri Sriwijaya.

[img]
Preview
Text (Cover)
COVER.pdf

Download (299kB) | Preview
[img]
Preview
Text (BAB I PENDAHULUAN)
BAB I.pdf

Download (82kB) | Preview
[img]
Preview
Text (BAB II TINJAUAN PUSTAKA)
BAB II.pdf

Download (533kB) | Preview
[img] Text (BAB III METODE PENELITAN)
BAB III.pdf
Restricted to Repository staff only

Download (255kB)
[img] Text (BAB IV PEMBAHASAN)
BAB IV.pdf
Restricted to Repository staff only

Download (293kB)
[img]
Preview
Text (BAB V KESIMPULAN DAN SARAN)
BAB V.pdf

Download (10kB) | Preview
[img]
Preview
Text (DAFTAR PUSTAKA)
DAFTAR PUSTAKA.pdf

Download (8kB) | Preview

Abstract

Short circuit fault current magnitude is affected by the disorder point distance, the greater distance the smaller the interference point of fault current in short circuited. Based on the analysis on the calculation of the value of setting Tms with existing field is still under appropriate conditions, the calculation of the value obtained at the feeders Banteng Tms OCR is 0.11 seconds while the data field is 0.1 seconds, and to the values calculated on the incoming side of the OCR Tms is 0,249 seconds while data in the field by 0.25 seconds. So also for the OCR setting on the incoming side is for the calculation of 952.63 A and for field of 1000 A. However, for the current setting of the OCR obtained at feeders is 609.125 A computed value that is much larger than the results on the field that is equal to 320 A . So it can be concluded that the existing OCR settings can not be said to be good setting in the field. Seen from Tms settings and current values, where the value of the setting on the feeder faster than setting the incoming. This is because if an interruption occurs, the feeders will be used to overcome the disorder so that interference can be minimized to the incoming side. Key word : Short Circuit, Tms Setting, Current Setting, Over Current Relay

Item Type: Thesis (Other)
Uncontrolled Keywords: Short Circuit, Tms Setting, Current Setting, Over Current Relay
Subjects: T Technology > TJ Mechanical engineering and machinery
Divisions: Telecommunication Engineering > Undergraduate Theses