ANALISA SUSUT TEGANGAN PADA PENYULANG ARWANA DI PT.PLN (PERSERO) RAYON AMPERA PALEMBANG MENGGUNAKAN ETAP 7.5

Jayanti, Novita (2014) ANALISA SUSUT TEGANGAN PADA PENYULANG ARWANA DI PT.PLN (PERSERO) RAYON AMPERA PALEMBANG MENGGUNAKAN ETAP 7.5. Other thesis, Politeknik Negeri Sriwijaya.

[img]
Preview
Text (COVER)
LA Cover.pdf

Download (275kB) | Preview
[img]
Preview
Text (BAB I PENDAHULUAN)
bab1 fix.pdf

Download (324kB) | Preview
[img]
Preview
Text (BAB II TINJAUAN PUSTAKA)
bab2 fix.pdf

Download (649kB) | Preview
[img] Text (BAB III METODE PENELITIAN)
bab3 fix.pdf
Restricted to Repository staff only

Download (568kB)
[img] Text (BAB IV PEMBAHASAN)
bab4 fix.pdf
Restricted to Repository staff only

Download (573kB)
[img]
Preview
Text (BAB V KESIMPULAN DAN SARAN)
bab5 fix.pdf

Download (166kB) | Preview
[img]
Preview
Text (DAFTAR PUSTAKA)
DAFTAR PUSTAKA.pdf

Download (86kB) | Preview

Abstract

Distribution systems are electrical systems which deliver power from generating electricity to consumers in a medium voltage scale to low voltage scale. The power plants located far from load centers, it results in considerable losses in the distribution of electrical power. The losses is caused by long enough power lines. Thus, the distribution of electrical power will experience a voltage drop along the line traversed. The report discusses the magnitude of the voltage susut, so it is can known at the end of the voltage feeders Arwana. From the results of calculations using the datum and supporting datum from ETAP 7.5 obtained voltage drop along the feeder Arwana at 2.79 % and then from the result of calculation using the formula obtained voltage drop along the feeder Arwana at 2,75 %. it shows that it still in the standard PLN (SPLN 72:1987) because it has not been over the prescribed standards which is voltage drop for feeders with maximum radial configuration forms at 5%. Voltage drop caused by the influence of the length of the feeder line. The longer the line and the electrical load used then the voltage drop that occurs will be bigger. And to cope drop voltage that happend at arwana feeders is used on load tap changer on power transformer. Keywords : Voltage Drop, Feeders, and Distribution Network 20kV

Item Type: Thesis (Other)
Uncontrolled Keywords: Voltage Drop, Feeders, and Distribution Network 20kV
Subjects: T Technology > TJ Mechanical engineering and machinery
Divisions: Telecommunication Engineering > Undergraduate Theses
Depositing User: Mrs Trisni Handayani
Date Deposited: 22 Jan 2016 03:05
Last Modified: 22 Jan 2016 03:05
URI: http://eprints.polsri.ac.id/id/eprint/440