MP, M. ADI NUGRAHA (2015) EVALUASI JARAK PENEMPATAN ARRESTER TERHADAP TRANSFORMATOR DAYA 30 MVA 70/20 KV PADA PT.PLN (Persero) GARDU INDUK BUKIT SIGUNTANG. Other thesis, Politeknik Negeri Sriwijaya.
|
Text (COVER)
COVER.pdf Download (56kB) | Preview |
|
|
Text (BAB I PENDAHULUAN)
BAB I.pdf Download (29kB) | Preview |
|
|
Text (BAB II TINJAUAN PUSTAKA)
BAB II.pdf Download (324kB) | Preview |
|
![]() |
Text (BAB III METEDOLOGI PENELITIAN)
BAB III.pdf Restricted to Repository staff only Download (166kB) |
|
![]() |
Text (BAB IV PEMBAHASAN)
BAB IV.pdf Restricted to Repository staff only Download (105kB) |
|
|
Text (BAB V KESIMPULAN DAN SARAN)
BAB V.pdf Download (24kB) | Preview |
|
|
Text (DAFTAR PUSTAKA)
DAFTAR PUSTAKA.pdf Download (14kB) | Preview |
Abstract
Lightning is the phenomena of nature are very dangerous . Even worse if the a bolt of lightning disrupt the system of electric power good that can cause voltage destructive more isolation equipment and could cause the occurrence of hyphen a short if a current of exceeding the limit of a current of about . Therefore on main station, fitted protection of a bolt of lightning namely lightning arrester. On a hill siguntang main station , a kind of arrester used is arrester eksplusi a kind of .From the results of reckoning the distances arrester the deployment of resources to a transformer 30 mva 70 / 20 kv in PT.PLN( persero ) main station hill siguntang is 4,37 meters. While which installed in the field is 3.5 meters. This must be known so that we can determine the distance that is effective in placement arrester against a transformer resources. Because if getting close arrester mounted , the more one is good too security against a bolt of lightning .
Item Type: | Thesis (Other) |
---|---|
Uncontrolled Keywords: | On a hill siguntang main station , a kind of arrester used is arrester eksplusi a kind of .From the results of reckoning the distances arrester the deployment of resources to a transformer 30 mva 70 / 20 kv in PT.PLN( persero ) main station hill siguntang is 4,37 meters. While which installed in the field is 3.5 meters. This must be known so that we can determine the distance that is effective in placement arrester against a transformer resources. Because if getting close arrester mounted , the more one is good too security against a bolt of lightning . |
Subjects: | T Technology > TJ Mechanical engineering and machinery T Technology > TK Electrical engineering. Electronics Nuclear engineering |
Divisions: | Electronic Engineering > Undergraduate Theses |
Depositing User: | Mrs Trisni Handayani |
Date Deposited: | 18 Nov 2015 08:49 |
Last Modified: | 18 Nov 2015 08:49 |
URI: | http://eprints.polsri.ac.id/id/eprint/1676 |